Fiberglass Shelter: Model ECS-F
|
Applications
 | Chemical Storage |
 | Chlorination Equipment |
 | Monitoring Equipment |
 | Generators |
 | Safety Showers |
 | Pumps |
 | Lift Stations |
 | Field Instruments |
 | Electronic Equipment |
 | Pollution Control/Monitoring Equipment
|
Standard Equipment
 | One exhaust fan providing complete air
change every minute |
 | Automatic-manual selector switch,
externally mounted and interlocked for automatic operation
of the exhaust fan and light when door is opened |
 | Door actuated microswitch for fan and
light |
 | Main electrical panel provided on the
wall with the following equipment wired and mounted on the
panel
 | Safety switch, 2 pole fused for 30
amps,120 volt 60 cycle, single phase |
 | Duplex electrical receptacle |
|
 | PVC light fixture(s) with covered bulb |
 | Heater, with thermostat appropriately
sized for each house |
|
Features
 | Gas tight gasketed door with safety chain |
 | Gas tight observation window on door |
 | Motorized intake louver for ventilation
with bug screens |
 | Lifting eyes for field installation |
 | Construction to withstand 150 mph wind
load |
 | Pitched roof to withstand 30 lbs./sq. ft.
snow load |
 | Large sub-panel with extra space for
field mounting of accessories
|
Options Available
 | Any non-standard power supply |
 | Mounting, wiring, and piping of any type
of equipment needed |
 | Motor starters, magnetic or manual |
 | Circuit breaker lighting distribution
panels |
 | High temperature safety override |
 | Exterior/Interior lighting |
 | Steel, wood, or fiberglass floor |
 | Special color |
 | Special holes, or plumbing connections |
 | Alarm lights, horns, and silencing
equipment |
 | Timer for exhaust fan |
 | Panic hardware/door closers |
 | Fan canopy |
 | Special lighting |
 | Special heating/cooling
|
|
Get a Quote
Download all of the AutoCAD drawings
for ECS buildings.
Click Here
For individual drawing files,
see comparison chart below.
|
| Model No. |
Width |
Length |
Height |
Weight |
Autocad Drawing |
| ECS-F64 |
6'-0" |
4'-0" |
7'-0" |
420 lbs. |
sd-176.exe |
| ECS-F66 |
6'-0" |
6'-0" |
7'-0" |
515 lbs. |
sd-177.exe |
| ECS-F68 |
6'-0" |
8'-0" |
7'-0" |
610 lbs. |
sd-178.exe |
| ECS-F610 |
6'-0" |
10'-0" |
7'-0" |
710 lbs. |
sd-184.exe |
| ECS-F612 |
6'-0" |
12'-0" |
7'-0" |
875 lbs. |
sd-185.exe |
| ECS-F614 |
6'-0" |
14'-0" |
7'-0" |
1100 lbs. |
sd-186.exe |
| ECS-F84 |
7'-6" |
4'-0" |
7'-0" |
525 lbs. |
sd-224.exe |
| ECS-F86 |
7'-6" |
6'-0" |
7'-0" |
630 lbs. |
sd-179.exe |
| ECS-F88 |
7'-6" |
8'-0" |
7'-0" |
715 lbs. |
sd-180.exe |
| ECS-F810 |
7'-6" |
10'-0" |
7'-0" |
775 lbs. |
sd-181.exe |
| ECS-F812 |
7'-6" |
12'-0" |
7'-0" |
835 lbs. |
sd-182.exe |
| ECS-F814 |
7'-6" |
14'-0" |
7'-0" |
895 lbs. |
sd-183.exe |
|
AutoCAD® version 14
or later is required to open the files from this site. |
SPECIFICATIONS
1.0 SCOPE - This
specification describes a Bevco House as manufactured by Bevco
Engineering Company, Inc., W222N5739 Miller Way, Sussex, WI
53089.
2.0 DESCRIPTION - The house
shall be completely assembled, ready to install, and capable of
housing any equipment as shown on the drawings. The Bevco House
shall be model ECS-F and shall be supplied with all components
factory mounted and wired.
3.0 DESIGN - The house shall be
a one piece molded fiberglass reinforced polyester (FRP)
construction with minimum wall, door, and roof thickness of 1".
Units with cemented or bolted end caps will not be accepted. The
house shall have a minimum of insulation to maintain a rating of
"R" 7.2. All materials are to be ultraviolet resistant and
the finished house, when installed in accordance with the
manufacturer's instructions, shall withstand 150 mph winds, and a 30
lb./sq. ft. snow load. The 36"x 6'6" door shall have
corrosion resistant hardware, and the door shall be provided with a
17"x 17" shatterproof window. The house shall be sized
width and lenght to order x 7' high at the peak, and shall be
shipped factory assembled and wired. Included shall be removable
lifting eyes and sufficient gasket and mounting flanges for direct
setting on concrete slab.
4.0 COMPONENTS - The house shall
have the following components factory mounted and wired in
non-conductive, non-corrosive electrical conduit boxes, and
fittings.
4.1 ELECTRICAL FIXTURES - The
following fixtures shall be provided: PVC light fixture(s) with
covered bulb. Exterior mounted weatherproof automatic manual
selector switch interlocked with a door operated micro switch to
operate the fan and lights either manually or automatically when the
door is opened. A 2 pole 120/60/1, fused safety switch of sufficient
size to handle the electrical accessories. Duplex receptacle(s) in
PVC weatherproof enclosure.
4.2 EXHAUST FAN AND INTAKE LOUVERS
- An exhaust fan shall be provided with gravity type louvers capable
of providing complete air change every minute. Intake air shall come
in through screened motorized intake louver of sufficient size to
allow the specified air change.
4.3 HEATER AND THERMOSTAT - A
heater and adjustable thermostat with sealed contacts of sufficient
size shall be provided.

Model ECS-F
| Model 7521-F | Model 7521-S
Model 7523-F | Model 7523-S | Model
PBF | Clamshell