Steel Shelter:
Model 7523-S
Applications
 | Chemical Storage |
 | Chorination Equipment
|
 | Monitoring Equipment
|
 | Generators
|
 | Pumps
|
 | Lift Stations
|
 | Field Instruments
|
 | Electronic Equipment
|
 | Pollution Control/Monitoring Equipment
|
Standard Equipment
 | One exhaust fan providing complete air
change every minute
|
 | Automatic-manual selector switch,
externally mounted and interlocked for automatic operation
of the exhaust fan and light when door is opened
|
 | Plastic bulkhead fittings for
chlorination vent and vacuum lines
|
 | Door actuated microswitch for fan and
light in gas compartment
|
 | Door actuated microswitch for light in
electrical compartment
|
 | Main electrical panel provided on the
wall with the following equipment wired and mounted on the
panel
 | Safety switch, 2 pole fused for 30
amps, 120 volt 60 cycle, single phase
|
 | Duplex electrical receptacle |
|
 | PVC light fixture(s) with covered bulb
|
 | Heater, with thermostat appropriately
sized for each house |
|
Features
 | Gas tight gasketed doors
|
 | Gas tight observation window on door
|
 | One intake louver for ventilation with
bug screens
|
 | Three point latch with key lock
|
 | Fire retarding insulation on all sides
|
 | Electrical power inlet connector (LB
Fitting)
|
 | Pitched roof to withstand 30 lbs./sq. ft.
snow load with drip lip
|
 | Vinyl covered floor
|
 | Large subpanel with extra space for field
mounting of accessories
|
 | Separate compartments for gas and gas
handling equipment and electrical/instrumentation
equipment
|
Options Available
 | Any non-standard power supply
|
 | Mounting, wiring, and piping of any type
of equipment needed
|
 | Motor starters, magnetic or manual
|
 | Circuit breaker lighting distribution
panels
|
 | High temperature safety override
|
 | Fan canopy
|
 | Special color
|
 | Special holes or plumbing connections
|
 | Alarm lights, horns, and silencing
equipment
|
 | Timer for exhaust fan
|
 | Exterior lighting |
|
Get a Quote
Download the AutoCAD drawing.
Click Here
AutoCAD® version 14 or later
is required to open the files from this site.
|
SPECIFICATIONS
1.0 SCOPE - This
specification describes a Bevco House as manufactured by Bevco
Engineering Company, Inc., W222N5739 Miller Way, Sussex, WI
53089.
2.0 DESCRIPTION - The house
shall be completely assembled, ready to install, and capable of
housing any equipment as shown on the drawings. The Bevco House
shall be model 7523-S and shall be supplied with all components
factory mounted and wired.
3.0 DESIGN - The house shall be
compartmentalized with two separate sections, one section for
chlorine or other equipment and the other section for electrical
equipment. The house shall be constructed of 12 gauge steel finished
with three coats of baked enamel or powered coated, hammertone
green, exterior finish. The floor shall be 11 gauge steel, provided
as an integral part of the house, and reinforced to support gas
cylinders or other heavy objects. The floor shall be vinyl covered.
The interior of the house shall be insulated with a 1" minimum
layer of plastic insulation. The plastic insulation shall meet U.L.
specifications for fire resistant SE-1 foam with an R-value of 7.2.
The house shall have dimensions of 67-1/4" wide, 29" deep,
by 81" high with predrilled holes for fastening to 1/2 inch
bolts preset in concrete. The roof shall be pitched and provided
with a drip lip. The side wall shall contain two screened vents, one
for an air inlet and one for exhaust. The house shall have two
independent, continuously hinged, three point latched doors. One
door shall have a key lock handle. On the chlorination compartment,
a gas tight window, 9"x7", shall be provided for
inspection of the interior with out opening the door.
4.0 COMPONENTS - The house shall
have the following components factory mounted and wired in
non-conductive, non-corrosive electrical conduit boxes and
fittings.
4.1 ELECTRICAL FIXTURES - The
following electrical fixtures shall be provided: PVC light fixture
with covered bulb. Exterior mounted, weatherproof, automatic-manual
selector switch, interlocked with a door actuated microswitch to
operate the fan and lights either manually or automatically when the
door is opened. A 2 pole 120/60/1, fused safety switch of sufficient
size to handle the electrical accessories. Duplex receptacle(s) in
PVC weatherproof enclosure.
4.2 EXHAUST FAN AND INTAKE LOUVERS
- An exhaust fan shall be provided with intake louvers capable of
providing complete air change every minute.
4.3 HEATER AND THERMOSTAT - A
heater and thermostat with sealed contacts of sufficient size shall
be provided.
4.4 MISCELLANEOUS - Plastic vent
and vacuum bulkhead fittings will be supplied.

Model ECS-F
| Model 7521-F | Model 7521-S
Model 7523-F | Model 7523-S | Model
PBF | Clamshell