Model 7523-F
SPECIFICATIONS
1.0 SCOPE - This
specification describes a Bevco House as manufactured by Bevco
Engineering Company, Inc., W222N5739 Miller Way, Sussex, WI
53089.
2.0 DESCRIPTION - The house
shall be completely assembled, ready to install, and capable of
housing any equipment as shown on the drawings. The Bevco House
shall be model 7523-F and shall be supplied with all components
factory mounted and wired.
3.0 DESIGN - The house shall be
compartmentalized with two separate sections, one section for
chlorine or other equipment and the other section for electrical
equipment. The house shall be of a one piece molded fiberglass
reinforced polyester (FRP). The floor shall be 11 gauge steel,
provided as an integral part of the house, and reinforced to support
gas cylinders or other heavy objects. The floor shall be vinyl
covered. The interior of the house shall be insulated with a 1"
minimum layer of plastic insulation. The plastic insulation shall
meet U.L. specifications for fire resistant SE -1 foam with an
R-value of 7.2. The house shall have dimensions of 67-1/4"
wide, 29" deep, by 81" high with pre-drilled holes for
fastening to 1/2 inch bolts preset in concrete. The roof shall be
pitched and provided with a drip lip. The side wall shall contain
two screened vents, one for an air inlet and one for exhaust. The
house shall have two independent, continuously hinged, three point
latched doors. One door shall have a key lock handle. On the
chlorination compartment, a gas tight window, 9"x7", shall
be provided for inspection of the interior with out opening the
door.
4.0 COMPONENTS - The house shall
have the following components factory mounted and wired in
non-conductive, non-corrosive electrical conduit, boxes and
fittings.
4.1 ELECTRICAL FIXTURES - The
following electrical fixtures shall be provided: PVC light fixture
with covered bulb. Exterior mounted, weatherproof, automatic-manual
selector switch interlocked with a door actuated microswitch to
operate the fan and lights either manually or automatically when the
door is opened. A 2 pole 120/60/1, fused safety switch of sufficient
size to handle the electrical accessories. Duplex receptacle(s) in
PVC weatherproof enclosure.
4.2 EXHAUST FAN AND INTAKE LOUVERS
- An exhaust fan shall be provided with intake louvers capable of
providing complete air change every minute.
4.3 HEATER AND THERMOSTAT - A
heater and thermostat with sealed contacts of sufficient size shall
be provided.
4.4 MISCELLANEOUS - Plastic vent
and vacuum bulkhead fittings will be supplied.