Need Answers Now?
Call 262-820-2400.
Contact Us



Bevco Engineering Company, Inc.
W222N5739 Miller Way
Sussex, WI 53089
Ph. 262-820-2400
Fax 262-820-2599




For all your material handling needs visit Babush Material Handling Systems, Inc.

Steel Shelter: Model 7521-S
    
Applications
bulletChemical Storage
bulletChorination Equipment
bulletMonitoring Equipment
bulletGenerators
bulletPumps
bulletLift Stations
bulletField Instruments
bulletElectronic Equipment
bulletPollution Control/Monitoring Equipment
  
Standard Equipment
bulletOne exhaust fan providing complete air change every minute
bulletAutomatic-manual selector switch, externally mounted and interlocked for automatic operation of the exhaust fan and light when door is opened
bulletPlastic bulkhead fittings for chlorination vent and vacuum lines
bulletDoor actuated microswitch for fan and light
bulletMain electrical panel provided on the wall with the following equipment wired and mounted on the panel
bulletSafety switch, 2 pole fused for 30 amps, 120 volt 60 cycle, single phase
bulletDuplex electrical receptacle
bulletPVC light fixture(s) with covered bulb
bulletHeater, with thermostat appropriately sized for each house
Features
bulletGas tight gasketed doors
bulletGas tight observation window on door
bulletOne intake louver for ventilation with bug screens
bulletThree point latch with key lock
bulletFire retarding insulation on all sides
bulletElectrical power inlet connector (LB Fitting)
bulletPitched roof to withstand 30 lbs./sq. ft. snow loadwith drip lip
bulletVinyl covered floor
bulletLarge subpanel with extra space for field mounting of accessories
   
Options Available
bulletAny non-standard power supply
bulletMounting, wiring, and piping of any type of equipment needed
bulletMotor starters, magnetic or manual
bulletCircuit breaker lighting distribution panels
bulletHigh temperature safety override
bulletFan canopy
bulletSpecial color
bulletSpecial holes or plumbing connections
bulletAlarm lights, horns, and silencing equipment
bulletTimer for exhaust fan
bulletExterior lighting

Get a Quote

Download the AutoCAD drawing.
Click Here

AutoCAD® version 14 or later is required to open the files from this site.

 

SPECIFICATIONS

1.0 SCOPE - This specification describes a Bevco House as manufactured by Bevco Engineering Company, Inc., W222N5739 Miller Way, Sussex, WI 53089. 

2.0 DESCRIPTION - The house shall be completely assembled, ready to install, and capable of housing any equipment as shown on the drawings. The Bevco House shall be model 7521-S and shall be supplied with all components factory mounted and wired. 

3.0 DESIGN - The house shall be constructed of 14 gauge steel, finished with three coats of baked enamel or powdered coated, hammertone green exterior finish. The floor shall be 11 gauge steel provided as an integral part of the house and reinforced to support gas cylinders or other heavy objects. The floor shall be vinyl covered. The interior of the house shall be insulated with a 1" minimum layer of plastic insulation. The plastic insulation shall meet U.L. specifications for fire resistant SE- 1 foam with an R-value of 7.2. The house shall have dimensions of 54" wide, 24" deep, by 72" high with predrilled holes for fastening to 1/2 inch bolts preset in concrete. The roof shall be pitched and provided with a drip lip.The side wall shall contain two screened vents, one for an air inlet and one for exhaust. The house shall have two independent continuously hinged, three point latched doors. One door shall have a key lock handle. A gas tight window, 9"x7", shall be provided for inspection of the interior without opening the door. 

4.0 COMPONENTS - The house shall have the following components factory mounted and wired in non-conductive, non-corrosive electrical conduit boxes and fittings. 

4.1 ELECTRICAL FIXTURES - The following electrical fixtures shall be provided: PVC light fixture with covered bulb. Exterior mounted, weatherproof, automatic-manual selector switch interlocked with a door actuated microswitch to operate the fan and lights either manually or automatically when the door is opened. A 2 pole 120/60/1, fused safety switch of sufficient size to handle the electrical accessories. Duplex receptacle(s) in PVC weatherproof enclosure. 

4.2 EXHAUST FAN AND INTAKE LOUVERS - An exhaust fan shall be provided with intake louvers capable of providing complete air change every minute. 

4.3 HEATER AND THERMOSTAT - A heater and thermostat with sealed contacts of sufficient size shall be provided. 

4.4 MISCELLANEOUS - Plastic vent and vacuum bulkhead fittings will be supplied.

 

horizontal rule

Model ECS-F  |  Model 7521-F  |  Model 7521-S
Model 7523-F  |  Model 7523-S  |  Model PBF | Clamshell

copyright ©2002-2006 Bevco Engineering Company, Inc.