Model 7521-F
Applications
 | Chemical Storage |
 | Chorination Equipment |
 | Monitoring Equipment |
 | Generators |
 | Pumps |
 | Lift Stations |
 | Field Instruments |
 | Electronic Equipment |
 | Pollution Control/Monitoring Equipment
|
Standard Equipment
 | One exhaust fan providing complete air
change every minute |
 | Automatic-manual selector switch,
externally mounted and interlocked for automatic operation
of the exhaust fan and light when door is opened |
 | Plastic bulkhead fittings for
chlorination vent and vacuum lines |
 | Door actuated microswitch for fan and
light |
 | Main electrical panel provided on the
wall with the following equipment wired and mounted on the
panel
 | Safety switch, 2 pole fused for 30
amps, 120 volt 60 cycle, single phase |
 | Duplex electrical receptacle |
|
 | PVC light fixture(s) with covered bulb |
 | Heater, with thermostat appropriately
sized for each house |
|
Features
 | Gas tight gasketed doors |
 | Gas tight observation window on
door
One intake louver for ventilation with bug screens |
 | Three point latch with key lock |
 | Fire retarding insulation on all sides |
 | Electrical power inlet connector (LB
Fitting) |
 | Pitched roof to withstand 30 lbs./sq. ft.
snow load with drip lip |
 | Vinyl covered floor |
 | Large subpanel with extra space for field
mounting of accessories
|
Options Available
 | Any non-standard power supply |
 | Mounting, wiring, and piping of any type
of equipment needed |
 | Motor starters, magnetic or manual |
 | Circuit breaker lighting distribution
panels |
 | High temperature safety override |
 | Fan canopy |
 | Special color |
 | Special holes or plumbing connections |
 | Alarm lights, horns, and silencing
equipment |
 | Timer for exhaust fan |
 | Exterior lighting |
|
Get a Quote
Download the AutoCAD drawing.
Click Here
AutoCAD® version 14 or later
is required to open the files from this site. |
SPECIFICATIONS
1.0 SCOPE - This
specification describes a Bevco House as manufactured by Bevco
Engineering Company, Inc., W222N5739 Miller Way, Sussex, WI
53089.
2.0 DESCRIPTION - The house
shall be completely assembled, ready to install, and capable of
housing any equipment as shown on the drawings. The Bevco House
shall be model 7521-F and shall be supplied with all components
factory mounted and wired.
3.0 DESIGN - The house shall be
of a one piece molded fiberglass reinforced (FRP). The floor shall
be 11 gauge steel provided as an integral part of the house and
reinforced to support gas cylinders or other heavy objects. The
floor shall be vinyl covered. The interior of the house shall be
insulated with a 1" minimum layer of plastic insulation. The
plastic insulation shall meet U.L. specifications for fire resistant
SE-1 foam with an R-value of 7.2. The house shall have dimensions of
54" wide, 24" deep, by 72" high with predrilled holes
for fastening to 1/2 inch bolts preset in concrete. The roof shall
be pitched and provided with a drip lip. The side wall shall contain
two screened vents, one for an air inlet and one for exhaust. The
house shall have two independent continuously hinged, three point
latched doors. One door shall have a key lock handle. A gastight
window, 9"x7", shall be provided for inspection of the
interior without opening the door.
4.0 COMPONENTS - The house shall
have the following components factory mounted and wired in
non-conductive, non-corrosive electrical conduit boxes and
fittings.
4.1 ELECTRICAL FIXTURES - The
following electrical fixtures shall be provided: PVC light fixture
with covered bulb. Exterior mounted weatherproof automatic-manual
selector switch interlocked with a door actuated micro switch to
operate the fan and lights either manually or automatically when the
door is opened. A 2 pole 120/60/1, fused safety switch of sufficient
size to handle the electrical accessories. Duplex receptacle(s) in
PVC weatherproof enclosure.
4.2 EXHAUST FAN AND INTAKE LOUVERS -
An exhaust fan shall be provided with intake louvers capable of
providing complete air change every minute.
4.3 HEATER AND THERMOSTAT - A
heater and thermostat with sealed contacts of sufficient size shall
be provided.
4.4 MISCELLANEOUS - Plastic vent
and vacuum bulkhead fittings will be supplied.

Model ECS-F
| Model 7521-F | Model 7521-S
Model 7523-F | Model 7523-S | Model
PBF | Clamshell
copyright ©2002-2006 Bevco